Loop Current Diagnostic

Where a measured loop current sits relative to live zero/full scale, with NAMUR-style band context — not a device verdict.

Instrumentation & ControlsElectrical & Power

Where a measured loop current sits relative to live zero/full scale, with NAMUR-style band context — not a device verdict.

App id: INST-39. Reference version 1.0.

How to fill it

Fill the inputs. The tool shows the outputs.

On the tool screen, Calc is the working sheet. Presets stores values you reuse. Reference is the formula, assumptions, and provenance below.

Formula

f = (I − 4 mA) / 16 mA

Inputs

NameUnit
Loop current (camera)mA
Live zero (optional)mA
Live full scale (optional)mA

Outputs

NameUnit
Span (hero result)%

Diagnose

Observations are context. They do not pass or fail a structure. See Diagnose.

WhenObservationSeverity
loop current < 3.6 mABelow 3.6 mAwarning
loop current < live zeroBelow live zerocaution
loop current > 21 mAAbove 21 mAwarning
loop current > live fullAbove live full scalecaution
loop current ≤ live fullIn measurement rangeinfo

Assumptions

  • Same scaling as INST-01. Use INST-01 when you only need percent span.

Provenance

  • NAMUR NE43 3.6 mA / 21 mA bands are common, not universal. Confirm the transmitter’s fault convention.