4–20 mA to Engineering Units

Linear transmitter current to process value. Engineering fields are pressure; use generic linear scaling for other quantities.

Instrumentation & ControlsFluid & PressureElectrical & Power

Linear transmitter current to process value. Engineering fields are pressure; use generic linear scaling for other quantities.

App id: INST-02. Reference version 1.0.

How to fill it

Fill the inputs. The tool shows the outputs.

On the tool screen, Calc is the working sheet. Presets stores values you reuse. Reference is the formula, assumptions, and provenance below.

Formula

EU = L + (I − 4)/16 × (H − L)

Inputs

NameUnit
Loop current (camera)mA
Lower range (LRV)psi
Upper range (URV)psi
Live zero (optional)mA
Live full scale (optional)mA

Outputs

NameUnit
Engineering value (hero result)psi
Span%

Diagnose

Observations are context. They do not pass or fail a structure. See Diagnose.

WhenObservationSeverity
loop current < 3.6 mABelow 3.6 mAwarning
loop current < live zeroBelow live zerocaution
loop current > 21 mAAbove 21 mAwarning
loop current > live fullAbove live full scalecaution
loop current ≤ live fullIn measurement rangeinfo
span fraction < 0 or span fraction > 1Outside configured spancaution

Assumptions

  • For temperature, flow, or raw counts use INST-04 / INST-06 / INST-16.

Provenance

  • Linear 4–20 mA transmitter. Pressure is the engineering dimension so mixed psi/kPa conversion works.