Instrumentation & Controls
RTD Resistance to Temperature
IEC 60751 Callendar–Van Dusen platinum RTD. Default R0 = 100 Ω (Pt100).
Instrumentation & ControlsThermal & HVAC
IEC 60751 Callendar–Van Dusen platinum RTD. Default R0 = 100 Ω (Pt100).
App id: INST-22. Reference version 1.0.
How to fill it
Fill the inputs. The tool shows the outputs.
On the tool screen, Calc is the working sheet. Presets stores values you reuse. Reference is the formula, assumptions, and provenance below.
Formula
R(T) = R0 (1 + A T + B T²) [T ≥ 0 °C]Inputs
| Name | Unit |
|---|---|
| Resistance (camera) | ohm |
| R0 (100 = Pt100) (optional) | ohm |
Outputs
| Name | Unit |
|---|---|
| Temperature (hero result) | C |
Diagnose
This tool does not attach diagnose observations.
Assumptions
- Leave R0 blank for Pt100. Enter 1000 Ω for Pt1000. Not a DIN 43760-only shortcut.
Provenance
- IEC 60751 A = 3.9083×10⁻³, B = −5.775×10⁻⁷, C = −4.183×10⁻¹². Below 0 °C uses the C term.