Fieldeng
Thermal & HVAC

Moist-Air Density

ρ = Pd/(Rd T) + Pv/(Rv T) with Rd = 287.05 J/kg·K and Rv = 461.495 J/kg·K.

Thermal & HVAC

ρ = Pd/(Rd T) + Pv/(Rv T) with Rd = 287.05 J/kg·K and Rv = 461.495 J/kg·K.

App id: THERM-14. Reference version 1.0.

How to fill it

Fill the inputs. The tool shows the outputs.

On the tool screen, Calc is the working sheet. Presets stores values you reuse. Reference is the formula, assumptions, and provenance below.

Formula

ρ = Pd / (Rd T) + Pv / (Rv T)

Inputs

NameUnit
Dry-bulb temperature (camera)C
Relative humidity%
Absolute pressure (optional)kPa

Outputs

NameUnit
Density (hero result)kg/m3

Diagnose

Observations are context. They do not pass or fail a structure. See Diagnose.

WhenObservationSeverity
RH > 0.7High relative humiditycaution
RH < 0.2Low relative humidityinfo

Assumptions

  • Leave pressure blank for 101.325 kPa.

Provenance

  • Feeds THERM-04 when you do not want the 1.204 kg/m³ default.

On this page