Thermal & HVAC
Moist-Air Enthalpy
h = 1.006 T + W (2501 + 1.86 T) kJ/kg with T in °C, per kg dry air. Approximate, not a certified property.
Thermal & HVAC
h = 1.006 T + W (2501 + 1.86 T) kJ/kg with T in °C, per kg dry air. Approximate, not a certified property.
App id: THERM-13. Reference version 1.0.
How to fill it
Fill the inputs. The tool shows the outputs.
On the tool screen, Calc is the working sheet. Presets stores values you reuse. Reference is the formula, assumptions, and provenance below.
Formula
h = cp,da T + W (h_fg,0 + cp,v T)Inputs
| Name | Unit |
|---|---|
| Dry-bulb temperature | C |
| Humidity ratio | kg/kg |
Outputs
| Name | Unit |
|---|---|
| Specific enthalpy (hero result) | kJ/kg |
Diagnose
This tool does not attach diagnose observations.
Assumptions
- Not for metering or certification.
Provenance
- Reference roughly 0 °C dry air. cp,da = 1.006 kJ/kg·K, h_fg,0 = 2501 kJ/kg, cp,v = 1.86 kJ/kg·K.