Fieldeng
Thermal & HVAC

Dew Point

Magnus dew point from dry-bulb temperature and relative humidity (a = 17.62, b = 243.12 °C).

Thermal & HVAC

Magnus dew point from dry-bulb temperature and relative humidity (a = 17.62, b = 243.12 °C).

App id: THERM-11. Reference version 1.0.

How to fill it

Fill the inputs. The tool shows the outputs.

On the tool screen, Calc is the working sheet. Presets stores values you reuse. Reference is the formula, assumptions, and provenance below.

Formula

Tdp = b γ / (a − γ);  γ = ln(RH) + a T / (b + T)

Inputs

NameUnit
Dry-bulb temperature (camera)C
Relative humidity (camera)%

Outputs

NameUnit
Dew point (hero result)C

Diagnose

Observations are context. They do not pass or fail a structure. See Diagnose.

WhenObservationSeverity
RH > 0.7High relative humiditycaution
RH < 0.2Low relative humidityinfo

Assumptions

  • RH is a fraction (enter %). RH = 0 is rejected because ln(0) is undefined.

Provenance

  • WMO Magnus over water. Valid roughly −45 °C to 60 °C. Not ice.