Darcy Friction Factor
Darcy friction factor: 64/Re when laminar, Haaland when Re ≥ 2300.
Fluid & Pressure
Darcy friction factor: 64/Re when laminar, Haaland when Re ≥ 2300.
App id: FLUID-06. Reference version 1.0.
How to fill it
Fill the inputs. The tool shows the outputs.
On the tool screen, Calc is the working sheet. Presets stores values you reuse. Reference is the formula, assumptions, and provenance below.
Formula
laminar f = 64/Re; turbulent 1/√f = −1.8 log10[(ε/(3.7D))^1.11 + 6.9/Re]Inputs
| Name | Unit |
|---|---|
| Reynolds number | 1 |
| Inside diameter | mm |
| Absolute roughness (optional) | mm |
Outputs
| Name | Unit |
|---|---|
| Darcy friction factor (hero result) | 1 |
| Relative roughness ε/D | 1 |
Diagnose
Observations are context. They do not pass or fail a structure. See Diagnose.
Screening bands in the app: Laminar · Transitional · Turbulent.
| When | Observation | Severity |
|---|---|---|
Reynolds number < 2300 | Laminar | info |
Reynolds number ≤ 4000 | Transitional | caution |
Reynolds number > 4000 | Turbulent | info |
relative > 0.05 | Very high relative roughness | caution |
Assumptions
- Darcy factor, not Fanning.
- Leave roughness blank for a smooth pipe (ε = 0).
- Transitional Re uses the Haaland branch.
Provenance
- Haaland, S. E. (1983). Simple and explicit formulas for the friction factor in turbulent pipe flow.